Life Safety
Across
- 2. Indicates a recommendation or that which is advised but not required.
- 6. A facility, building, or structure used to house chambers and all auxiliary service equipment for medical applications and procedures at pressure above normal atmospheric pressure.
- 7. Required extinguisher type for a grease in a commercial kitchen.
- 11. An organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure.
- 12. Required every 12 years on fire extinguishers to ensure the cylinder is safe.
- 13. An opening in a fire-rated assembly that must be properly sealed to maintain its integrity.
- 17. These doors must latch, be self-closing, and bear a visible label.
- 21. Categories shall be determined by following and documenting a defined procedure to determine a level hazard.
- 22. Acronym used during a fire emergency for staff response.
- 25. The continuous and unobstructed path of travel to leave a building in an emergency.
- 26. Manual device used to activate a fire alarm system.
- 28. Describes the required interval for code-compliant maintenance tasks.
- 29. A test instrument designed to continually check the balanced and unbalanced impedance from each line of an isolated circuit to ground and equipped with a built-in test circuit to exercise the alarm without adding to the leakage current hazard. (ELS)
- 30. Required in healthcare facilities to provide emergency power to life safety, critical, and equipment branches.
- 32. Program required when any life safety system is out of service for more than 4 or 10 hours.
Down
- 1. Substance used to seal penetrations in rated fire barriers.
- 3. Term used when a required fire or life safety component does not meet code or performance expectations.
- 4. The maximum time, in seconds, that the EPSS will permit the load terminals of the transfer switch to be without acceptable electrical power.
- 5. The NFPA code that addresses building construction, protection, and occupancy features to minimize danger to life from fire.
- 8. It displays the location of an alarm condition in a fire alarm system.
- 9. The process of transferring a medical gas in gaseous or liquid state from one container or cylinder to another container or cylinder (MED).
- 10. You must do this to prove that inspections, tests, and maintenance occurred.
- 14. The minimum clearance (in inches) required below a sprinkler head.
- 15. Required illumination duration (in minutes) for emergency lighting during power failure.
- 16. The acronym used to describe how to operate a portable fire extinguisher.
- 18. A fire alarm signal indicating a condition that needs attention but isn’t an alarm.
- 19. Class extinguisher for flammable liquids, combustible liquids, petroleum greases, tars, oils, oil-based paints, solvents, lacquers, alcohols, and flammable gases.
- 20. The process of capturing and carrying away gases vented from the patient breathing circuit during the normal operation of gas anesthesia or analgesia equipment.
- 23. The section of the code and standards that is provided for guidance and explanatory material.
- 24. Indicates a mandatory requirement.
- 25. The final door or opening in the egress path leading out of the building.
- 27. Type of material that expands when exposed to heat, sealing gaps in fire barriers.
- 31. Fire sprinkler heads must not have this on them unless it is from the manufacturer.