May 2025
Across
- 2. NFPA 15 is the Standard for Water _____ Fixed Systems for Fire Protection
- 3. During a flow test of a Water Spray Fixed System ______ shall be recorded at the hydraulically remote nozzle
- 5. When performing an underwater evaluation on a tank, ____ shall be removed before beginning
- 8. NFPA 22 is the Standard for Water _____ for Private Fire Protection
- 11. A _____ tank provides a separation between a fire pump and a city water supply
- 12. A Water Mist system shall have a water supply capable of supplying water for a minimum duration of _____ minutes.
- 13. A tank's water level should never get more than _____ inches below the designated service level to be considered full
- 14. The exterior of the tank, supporting structure, vents, foundation, and catwalks or ladders, where provided, shall be inspected _______ for signs of obvious damage or weakening
Down
- 1. _______ in 1940, NFPA 13A was the original basis for what is now NFPA 25
- 4. A tanks water level is required to be inspected ______ when not equipped with supervised water level alarms
- 6. Automatic water mist nozzles that have been installed for _____ years shall be replaced, or representative samples shall be tested and then retested at 5-year intervals.
- 7. ______, a water tank used to supply a water mist system shall be drained and refilled
- 9. _____ tanks rely on elevation to provide necessary pressure to the fire protection system
- 10. NFPA 750 is the Standard on _____ Mist Fire Protection Systems
- 13. When a Water Spray Fixed System is equipped with a heat detection system, NFPA states that it shall operate within ____ seconds